Data Logging Suggestions

Any Modbusi register can be logged as any one of the 20 datalog channels provided. The particular registers you chose will depend upon your application and your objectives. The relevance of each parameter to that application will change as the project progresses and points of interest are discovered and optimised. If the Meter is being used to profile energy usage, for example, then the kwh readings alone may suffice. These energy totals each require two datalog channel for the full measurement resolution to be realised.

The new Digital Inputs available on versions of the Cube 400 can be wired to count pulses from modern water and gas meters to show water and gas consumption profiles. Electricity, water and gas profiles can then be analysed together to produce an all encompasing report.

The table below demonstrates how the data log table may be poulated to record key energy values for a three phase supply. Channels 16 to 20 are designated as scale factor channels so that the correct scales may be applied to the compact integer values being logged. ( As channel 18 is not required in this instance it could be replaced with 7691, Phase 1 volts, to fully utilise the set.)

The term Demand can loosely be interpreted as meaning average. The demand period must be set up in the Setup.html page to be the same as the datalog period. This ensures that the average value is calculated for exactly the same time interval as the time between data is logs. If demand values are not chosen then instantaneous values will be used and they will not be representative of the value throughout the log interval.

The flexibility that the data log table provides is one of the strengths of the meter, used carefully, the benefits of a comprehensive report can be produced for any situation.

Sample Data Log Table.

Data Log
Channel No.

Data
Address

Data

Scaling

1

7680

KWh High Word

eScale

2

7681

KWh Low Word

3

7684

Kvarh High Word

eScale

4

7685

Kvarh Low Word

5

6656

Digital Input High Word

 

6

6657

Digital Input Low Word

7

6658

Digital Input High Word

 

8

6659

Digital Input Low Word

9

7714

Phase 1 Amps Demand

Ki

10

7715

Phase 2 Amps Demand

11

7716

Phase 3 Amps Demand

12

7726

kW Demand

Kp-1

13

7727

kVA Demand

14

7701

System Power Factor

1000 = 1.000

15

7732

Neutral Current

Ki

16

7733

Amps Scale Ki

-

17

7734

Phase Volts Scale Kvp

-

18

7735

Line Volts Scale Kvl

-

19

7736

Power Scale Kp

-

20

7737

Energy Scale Ke

-

 


Product overview
  • Webserver
  • Automatically Control
    • Heaters
    • Coolers
    • Humidity
    • Lighting
  • Power over Etherneti
  • Universal Input
  • Contact Output
  • New Linear Output
  • New Solid State Relay Output
  • New Autotune PIDi Control
  • AJAXi technology
  • Modbusi TCP/IP
  • Graph Plotting
  • Datalogging